Function description – Temperature control
Addressing
Enter a description to help identify the probe, for example the name of the room where it is installed
The probe can be used as a Master or a Slave probe in a MyHOME system (in case of Slave probe, only enter the address of the Master probe the Slave probe must be associated to)
Set the type of system: heating, cooling, or both
Enter the ID code found on the device, or obtained using the Bus Scanner function
Enter the system address of the probe (1 to 99)
Up to 9 slave probes can be assigned to a master probe, enter their number here
Type of system
Select the type of hydraulic system (depending the device installed and the type of control) among the ones in the list
Actuators and pumps
In this field add the actuators that will be managed by the probe, indicating the number (1 to 9) and the function
The same setting must also be completed for the circulation pumps
There is also the possibility of setting the delay for the activation of the pumps, separated for heating and cooling
Set point
You can change the preset temperature values for the Thermal protection and the Antifreeze modes
The factory settings are the following:
Thermal protection
35 °C
Antifreeze
7 °C
General settings
Enabling of the zone status indication LED
You can set a fan-coil activation delay both for the heating and the cooling functions
Regulation band
The probe has a basic tolerance setting in relation to the set point defined (hysteresis); this tolerance value can be changed with values between 0.1° and 0.5°; increasing the value will increase the tolerance in relation to the set point, but the switching on and off frequency will be reduced
With systems with fan-coils it is possible to also set the temperature deviation that will cause the change of the speed of the fan-coil